Combination fire protection block
For detailed information, other images and documents, please select individual articles from the following table.
Combination fire protection block
For sealing square openings in the fire resistance class "fire resistant".
Exclusively for trade customers
Register now and access more than 125,000 products
Variants
Exclusively for trade customers
Register now and access more than 125,000 products
- Quick to install.
- Simple and cost-effective.
- Easy retrofitting.
- Free of halogen and solvents.
- Additional cables/pipes can be retrofitted at any time.
Proof of Performance
- Wall and ceiling ducts, fire-resistant, fire protection blocks, fire-resistant Z-19.53-2374
- Product approval Combi fire protection compound Z-19.11-2101
Application area
Clean opening.
Cut and bring fire protection stones according to the occupancy.
Fill remaining gap and spaceswith fire protection putty.
Affix ID plate.
- Wall and ceiling ducts, fire-resistant, fire protection blocks, fire-resistant Z-19.53-2374
- Product approval Combi fire protection compound Z-19.11-2101
Application area
- For processing in the system [E1.1] Fire protection blocks and stoppers [E1.1].
- Fire resistance class "fire resistant".
- For wall and floor penetration firestops for electrical lines and for copper pipes up to 28 mm in diameter or steel pipes up to 54 mm in diameter (pipes with blocks only).
Instructions
- Fire-retardant plugs are simply selected according to the diameter of the core drill hole and installed in both sides of the wall or ceiling, and the space between cables is closed with the Combi fire protection compound.
- Rectangular openings are closed off with the fire-retardant blocks. These must be installed tautly and in layers with an offset of the vertical joints.
Select RAL-colour code
!! NOTE: On-screen visualisation of the colour differs from real colour shade!!